Humidifying Air with Steam - SI units

The amount of vapor - kg per cubic meter - in humid air

Sponsored Links

The table below can be used to estimate the amount of vapor in an air volume of 100 m3:

Vapor in Air (kg per 100 m3airflow)
Dry Temperature (oC) Relative Humidity (%)
100 85 80 75 70 65 60 55 50 45 40 35 30
32 3.39 2.89 2.72 2.55 2.38 2.19 2.04 1.93 1.7 1.53 1.36 1.19 1.02
31 3.22 2.73 2.57 2.41 2.25 2.1 1.93 1.77 1.61 1.45 1.29 1.13 0.97
30 3.05 2.59 2.44 2.29 2.13 1.97 1.83 1.67 1.52 1.37 1.22 1.07 0.91
29 2.89 2.45 2.31 2.17 2.02 1.88 1.73 1.59 4.45 1.3 1.16 1.01 0.87
28 2.73 2.32 2.19 2.05 1.91 1.78 1.64 1.5 1.37 1.23 1.1 0.96 0.82
27 2.59 2.2 2.07 1.94 1.81 1.68 1.55 1.42 1.29 1.16 1.03 0.91 0.78
26 2.45 2.08 1.96 1.83 1.71 1.59 1.47 1.34 1.22 1.1 0.97 0.86 0.73
25 2.31 1.97 1.85 1.73 1.62 1.5 1.39 1.27 1.16 1.04 0.93 0.81 0.69
24 2.19 1.86 1.75 1.64 1.53 1.42 1.31 1.2 1.09 0.98 0.87 0.77 0.66
23 2.06 1.76 1.63 1.55 1.45 1.34 1.24 1.14 1.03 0.93 0.83 0.72 0.62
22 1.95 1.66 1.56 1.46 1.36 1.27 1.17 1.07 0.98 0.88 0.78 0.68 0.59
21 1.84 1.56 1.47 1.38 1.29 1.2 1.1 1.02 0.92 0.83 0.74 0.67 0.55
20 1.74 1.48 1.39 1.3 1.22 1.13 1.04 0.98 0.87 0.78 0.69 0.61 0.52
19 1.63 1.39 1.31 1.23 1.15 1.06 0.98 0.9 0.82 0.74 0.65 0.57 0.49
18 1.54 1.31 1.24 1.16 1.08 1 0.93 0.85 0.77 0.69 0.62 0.54 0.46
17 1.45 1.24 1.16 1.09 1.02 0.94 0.87 0.8 0.73 0.65 0.59 0.51 0.44
15 1.29 1.1 1.03 0.97 0.9 0.84 0.77 0.71 0.66 0.58 0.52 0.45 0.39
10 0.94 0.8 0.76 0.71 0.66 0.61 0.57 0.52 0.47 0.43 0.38 0.33 0.28
0 0.49 0.41 0.39 0.37 0.34 0.32 0.29 0.27 0.24 0.22 0.2 0.17 0.15
-5 0.33 0.28 0.26 0.25 0.23 0.21 0.2 0.18 0.16 0.15 0.13 0.11 0.1
-10 0.22 0.18 0.17 0.16 0.15 0.14 0.13 0.12 0.11 0.1 0.09 0.08 0.06

Note! In psychrometric charts and Mollier diagram the amount of vapor is given in kg/kg dry air. The values from the table above can be transformed dividing by the air density at the actual temperature.

Example - Humidifying Air with Steam

Air at 20oC and 30% relative humidity are humidified to 20oC and 80% relative humidity.

From a table above air at 20oC and 30% relative humidity contains 0.52 kg water vapor per 100 m3 air flow.Air at 20oC and 80% relative humidity contains 1.39 kgper 100 m3 air flow.

The amount of water vapor needed can be calculated as:

Amount of Water Vapor = ((1.39 kg) - (0.52 kg))

= 0.87 kgis the amount of water vapor necessary for an air volume of 100 m3.

Sponsored Links


ToolBox ShortList

Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!

Add this Page!Delete the ShortList!

Google
Web The HVAC ToolBox

Free Translation
Translate this page to Spanish French German Italian Dutch Norwegian

© The HVAC ToolBox

The content in The HVAC ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.

We appreciate any comments and tips on how to make The HVAC ToolBox a better information source. Please contact us by email if You find any faults, inaccurate, or otherwise unacceptable information.

Editor email

5 12 1