Static pressures in HVAC system avoids the tops of the systems drying out
Sponsored Links
The static pressure of most HVAC systems consists of the height of the building plus a cushion at the top of the building. In general the cushion is around 5 - 10 psi (lb/in2), 10 - 20 ft (3 - 6 m) water column.
The static pressure can be expressed as head:
hs = hb + hc (1)
where
hs = static head (ft, m)
hb = elevation at the top of the building (ft, m)
hc = cushion required at the top of the tallest building (ft, m)
It is often common to express static pressure in psi:
ps = hb + hc / (144 / γ) (2)
where
ps = static pressure (psig)
γ = specific weight of water at the operating temperature (lb/ft3)
The static pressure of a 190 ft tall building and cushion head 10 ft can be expressed as head:
hs = (200 ft) + (20 ft)
= 220 ft
If the water operating temperature is 60oF with specific weight of 62,4 lb/ft3 - the pressure in psig can be expressed as:
ps = (200 ft) + (20 ft) / (144 / (62,4 lb/ft3) )
= 95,3 psig
Sponsored Links
Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!
Translate this page to
Spanish
French
German
Italian
Dutch
Norwegian
© The HVAC ToolBox
The content in The HVAC ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.
We appreciate any comments and tips on how to make The HVAC ToolBox a better information source. Please contact us by email if You find any faults, inaccurate, or otherwise unacceptable information.
5 12 1
View Engineering, Design and Construction news in the absolute FREE Automatic WebSite Viewer. Engineering Breaking News!