Safety Valves and Relief Capacity

Maximum safety valves free air relief capacity

Sponsored Links

The table below can be use to determine the maximum relief free air capacity of safety valves:

Maximum Relieving Capacity of Free Air (ft3/min)
Valve
Diameter (inches)
Gauge Pressure (psi)
50 100 150 200 250 300 350 400 500 600 800 1000 1200 1600 2000 2400
1/4 12 20 27 33 38 43 48 53 61 70 84 97 109 128 147 160
3/8 17 27 36 44 51 58 65 72 83 95 115 133 149 176 197 215
1/2 20 32 42 51 59 67 74 111 129 147 177 205 230 270 304 330
3/4 37 59 78 96 112 127 141 176 224 232 242 346 386 423 474 518
1 58 94 124 152 178 202 224 248 286 324 390 450 500 586
1 1/4 84 135 180 221 259 293 325 352 400 443 509
1 1/2 114 186 248 302 354 400 444 478 528 568 634
2 189 306 410 501 592 668 741
2 1/2 282 457 613 750 880 998 1114
3 393 638 856 1050 1230 1398 1557

The relief capacity of a safety valve depends on the

A relief valve must be capable of relieving the capacity of the connected compressor(s) at operating pressure. Note that the relief pressure can not be set higher than the maximum rated working pressure of any equipment in the system. If the operating pressure is right below the relief pressure of the valve, the valve may start leaking.

As a "rule of thumb" it is common to set the relief pressure 10% above the working pressure of the system.

Sponsored Links


ToolBox ShortList

Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!

Add this Page!Delete the ShortList!

Google
Web The HVAC ToolBox

Free Translation
Translate this page to Spanish French German Italian Dutch Norwegian

© The HVAC ToolBox

The content in The HVAC ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.

We appreciate any comments and tips on how to make The HVAC ToolBox a better information source. Please contact us by email if You find any faults, inaccurate, or otherwise unacceptable information.

Editor email

5 12 1