Approximate Heat Gain from Occupants in Air Conditioned Spaces - in btu/hr
Sponsored Links
The table below can be used to estimate the sensible and latent heat from people. The values can be used to calculate the heat load handled by the air condition system.
| Typical Application | Sensible Heat
(btu/hr) |
Latent
Heat
(btu/hr) |
| Theater-Matinee | 200 | 130 |
| Theater-Evening | 215 | 135 |
| Offices, Hotels, Apartments | 215 | 185 |
| Retail & Department Stores | 220 | 230 |
| Drug Store | 220 | 280 |
| Bank | 220 | 280 |
| Restaurant | 240 | 310 |
| Factory | 240 | 510 |
| Dance Hall | 270 | 580 |
| Factory | 330 | 670 |
| Bowling Alley | 510 | 940 |
| Factory | 510 | 940 |