Air velocities due to natural draught caused by the indoor hot and outdoor cold temperature difference
Sponsored Links
The air velocity caused by the forces created by the difference in density of cold and warm air, can be expressed as
v = 4.43 ( h (th - to )/ (273 + to) )1/2 (1)
where
v = theoretical velocity (m/s)
h = height of air column (m)
th = temperature hot air column (oC)
to = outside temperature (oC)
The velocities in columns of different heights and at different hot temperatures are shown in the table below. The calculations are made for an outside temperature to = 0oC.
| Velocity of Air - v - (m/s) | ||||||
| Height
of Column
- h - (m) |
Temperature of Hot Column - th - (oC) | |||||
| .4. | .8. | .16. | .32. | .64. | .128. | |
| .0.2. | .0.24. | .0.34. | .0.48. | .0.68. | .0.96. | .1.36. |
| .0.4. | .0.34. | .0.48. | .0.68. | .0.96. | .1.36. | .1.92. |
| .0.8. | .0.48. | .0.68. | .0.96. | .1.36. | .1.92. | .2.71. |
| .1.6. | .0.68. | .0.96. | .1.36. | .1.92. | .2.71. | .3.84. |
| .3.2. | .0.96. | .1.36. | .1.92. | .2.71. | .3.84. | .5.43. |
| .6.4. | .1.36. | .1.92. | .2.71. | .3.84. | .5.43. | .7.67. |
| .12.8. | .1.92. | .2.71. | .3.84. | .5.43. | .7.67. | .10.85. |
| .25.6. | .2.71. | .3.84. | .5.43. | .7.67. | .10.85. | .15.35. |
| .51.2. | .3.84. | .5.43. | .7.67. | .10.85. | .15.35. | .21.71. |
Sponsored Links
Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!
Translate this page to
Spanish
French
German
Italian
Dutch
Norwegian
© The HVAC ToolBox
The content in The HVAC ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.
We appreciate any comments and tips on how to make The HVAC ToolBox a better information source. Please contact us by email if You find any faults, inaccurate, or otherwise unacceptable information.
5 12 1
View Engineering, Design and Construction news in the absolute FREE Automatic WebSite Viewer. Engineering Breaking News!