The overall heat loss from a building can be calculated as
H = Ht + Hv + Hi (1)
where
H = overall heat loss (W)
Ht = heat loss due to transmission through walls, windows, doors, floors and more (W)
Hv = heat loss caused by ventilation (W)
Hi = heat loss caused by infiltration (W)
The heat loss through walls, windows, doors, ceilings, floors etc. can be calculated as
Ht = A U (ti - to) (2)
where
Ht = transmissionheat loss (W)
A = area of exposed surface (m2)
U = overall heat transmission coefficient (W/m2K)
ti = inside air temperature (oC)
to= outside air temperature (oC)
Heat loss through roofs should be added 15% extra because of radiation to space. (2) can be modified to:
H = 1.15 A U (ti - to) (2b)
For walls and floors against earth (2) should be modified with the earth temperature:
H = A U (ti - te) (2c)
where
te= earth temperature (oC)
The overall of heat transmission coefficient - U - can be calculated as
U = 1 / (1 / fi + x1 / k1 + x2 / k2+ x3 / k3 +..+ 1 / fo) (3)
where
fi = surface conductance for inside wall (W/m2K)
x = thickness of material (m)
k = thermal conductivity material (W/mK)
fo= surface conductance for outside wall (W/m2K)
The conductance of a building elements can be expressed as:
C = k / x (4)
where
C = conductance, heat flow through unit area in unit time (W/m2K)
The thermal resistivity of the building element can be expressed as:
R = x / k = 1 / C (5)
where
R = thermal resistivity (m2K/W)
Using (4) and (5), (3) may be modified to
1 / U = Ri + R1 + R2 + R3 + .. + Ro (6)
For walls and floors against earth (6) should be modified to
1 / U = Re + SR (6b)
The heat loss due to ventilation without heat recovery can be expressed as:
Hv = cp ρ qv (ti - to) (7)
where
Hv = ventilationheat loss (W)
cp = specific heat capacity of air (J/kg/K)
ρ = density of air (kg/m3)
qv = air volume flow (m3/s)
ti = inside air temperature (oC)
to = outside air temperature (oC)
The heat loss due to ventilation with heat recovery can be expressed as:
Hv = (1 - β / 100) cp ρ qv (ti - to) (7)
where
β = heat recovery efficiency (%)
An heat recovery efficiency of approximately 50% is common for a normal cross flow heat exchanger. For a rotating heat exchanger the efficiency my exceed 80%.
Due to leakages in the building construction, opening and closing of windows, etc. the air in the building shifts. As a rule of thumb the number of air shifts is often set to 0.5 per hour. The value is hard to predict and depend of several variables - wind speed, difference between outside and inside temperatures, the quality of the building construction etc.
The heat loss caused by infiltration can be calculated as
Hi = cp ρ n V (ti - to) (8)
where
Hi = heat lossinfiltration (W)
cp = specific heat capacity of air (J/kg/K)
ρ = density of air (kg/m3)
n = number of air shifts, how many times the air is replaced in the room per second (1/s) (0.5 1/hr = 1.4 10-4 1/s as a rule of thumb)
V = volume of room (m3)
ti = inside air temperature (oC)
to = outside air temperature (oC)
Sponsored Links
Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!
Translate this page to
Spanish
French
German
Italian
Dutch
Norwegian
© The HVAC ToolBox
The content in The HVAC ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.
We appreciate any comments and tips on how to make The HVAC ToolBox a better information source. Please contact us by email if You find any faults, inaccurate, or otherwise unacceptable information.
5 12 1
View Engineering, Design and Construction news in the absolute FREE Automatic WebSite Viewer. Engineering Breaking News!