Support Ductwork

Ductwork support and recommended spacing between hangers

Sponsored Links

Support spacing for the ductwork is typical based upon deflection, stress and cylinder buckling analysis. For sheet metal ductwork the spacing between hangers should not exceed the maximum distances listed in the table below.

Horizontal Ductwork

Ducts Size
(Sq.Ft)
Maximum Spacing
(Feet)
less than 4 8
4 to 10 6
more than 10 4

Vertical Ductwork

Ducts Type Maximum Spacing
(Feet)
round 12
rectangular 10