HVAC Systems and Applications! - Resources, Tools and Basic Information for Engineering and Design.
Hot water heat carrying capacity of copper tube type L
Sponsored Links
Copper tubes is common in heating systems, especially connecting heating elements as radiators, fan units and similar elements. The table below can be used to estimate heat carrying capacity of copper tubes type L:
| Hot Water Heat Carrying Capacity of Type L Copper Tube (Btu * 1000 per hour) 1) | ||||||||||||
| Nominal tube size (inch) | Friction Head (milli inches per foot of tube) | |||||||||||
| 420 | 600 | 480 | 360 | 300 | 240 | 180 | 150 | 120 | 90 | 75 | 60 | |
| 3/8 | 10 | 9 | 8 | 7 | 6 | 5.5 | 4.5 | 4 | 3.5 | 3 | 3 | 2.5 |
| 1/2 | 20 | 18 | 16 | 13.5 | 12 | 11 | 9 | 8 | 7 | 6 | 5 | 5 |
| 5/8 | 36 | 30 | 26 | 22 | 20 | 18 | 15 | 13 | 12 | 10 | 9 | 8 |
| 3/4 | 51 | 46 | 40 | 34 | 31 | 28 | 23 | 21 | 18 | 15 | 14 | 12 |
| 1 | 104 | 94 | 82 | 70 | 63 | 56 | 47 | 42 | 37 | 32 | 28 | 25 |
| 1 1/4 | 185 | 169 | 149 | 125 | 112 | 100 | 84 | 75 | 66 | 56 | 50 | 44 |
| 1 1/2 | 300 | 270 | 235 | 200 | 180 | 160 | 134 | 120 | 105 | 90 | 81 | 71 |
| 2 | 625 | 560 | 495 | 420 | 375 | 335 | 2580 | 250 | 200 | 188 | 170 | 150 |
| 2 1/2 | 1130 | 1010 | 890 | 750 | 680 | 600 | 500 | 450 | 395 | 335 | 305 | 270 |
| 3 | 1840 | 1650 | 1450 | 1210 | 1100 | 980 | 820 | 740 | 650 | 550 | 490 | 420 |
| 3 1/2 | 2750 | 2480 | 2170 | 1840 | 1650 | 1450 | 1210 | 1100 | 980 | 820 | 740 | 650 |
| 4 | 3900 | 3500 | 3100 | 2600 | 2350 | 2090 | 1760 | 1580 | 1390 | 1180 | 1080 | 950 |
1) The table is designed for a temperature of 20oF drop in radiators and heating elements. For other temperature drops the values must be changed accordingly. With temperature drop 10oF the capacities must be multiplied with 0.5.
Sponsored Links
Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!
Translate this page to
Spanish
French
German
Italian
Dutch
Norwegian
© The HVAC ToolBox
The content in The HVAC ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.
We appreciate any comments and tips on how to make The HVAC ToolBox a better information source. Please contact us by email if You find any faults, inaccurate, or otherwise unacceptable information.
5 12 1
View Engineering, Design and Construction news in the absolute FREE Automatic WebSite Viewer. Engineering Breaking News!