Latent and sensible cooling and heating equations - in imperial units
Sponsored Links
The sensible heat in a heating or cooling process of air can be expressed as:
hs = 1.08 q dt (1)
where
hs = sensible heat (btu/hr)
q = air volume flow (cfm, cubic feet per minute)
dt = temperature difference (oF)
The latent heat due to moisture in the air can be expressed as:
hl = 0.68 q dwgr (2)
or
hl = 4,840 q dwlb (3)
where
hl= latent heat (btu/hr)
q = air volume flow (cfm, cubic feet per minute)
dwgr = humidity ratio difference (gram water/lb dry air)
dwlb = humidity ratio difference (lb water/lb dry air)
Total heat due to both temperature and moisture can be expressed as:
ht = 4.5 q dh (4)
where
ht= total heat (btu/hr)
q = air volume flow (cfm, cubic feet per minute)
dh = enthalpy difference (btu/lb dry air)
Total heat can also be expressed as:
ht = hs + hl
= 1.08 q dt + 0.68 q dwgr (4)
An air flow of one cfm is heated from 32 to 52oF. Using (1) the sensible heat added to the air can be expressed as:
hs = 1.08 1(cfm) (52 - 32)(oF)
= 21.6 (btu/hr)
Sponsored Links
Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!
Translate this page to
Spanish
French
German
Italian
Dutch
Norwegian
© The HVAC ToolBox
The content in The HVAC ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.
We appreciate any comments and tips on how to make The HVAC ToolBox a better information source. Please contact us by email if You find any faults, inaccurate, or otherwise unacceptable information.
5 12 1
View Engineering, Design and Construction news in the absolute FREE Automatic WebSite Viewer. Engineering Breaking News!