Clean Rooms - ISO Standard 14644

Clean room class limits according ISO Standard 14644-1

Sponsored Links

Clean room maintained virtually free of contaminants, such as dust or bacteria, are used in laboratory work and in the production of precision parts for electronic or aerospace equipment.

In the clean room standard ISO 14644-1 "Classification of Air Cleanliness" the classes are based on the formula

Cn = 10N (0.1/D)2.08 (1)

where

Cn = maximum permitted number of particles per cubic meter equal to or greater than the specified particle size, rounded to whole number

N = is the ISO class number, which must be a multiple of 0.1 and be 9 or less

D = is the particle size in micrometers

ISO
Class
Maximum Number of Particles in Air
(particles in each cubic meter
equal to or greater than the specified size)
> 0.1 μm > 0.2 μm > 0.3 μm > 0.5 μm > 1 μm > 5 μm
ISO Class 1 10 2
ISO Class 2 100 24 10

4

ISO Class 3 1000 237 102 35 8
ISO Class 4 10,000 2,370 1,020 352 83
ISO Class 5 100,000 23,700 10,200 3,520 832 29
ISO Class 6 1,000,000 237,000 102,000 35,200 8,320 293
ISO Class 7 352,000 83,200 2930
ISO Class 8 3,520,000 832,000 29,300
ISO Class 9 35,200,000 8,320,000 293,000

ISO Cleanroom Standards

Sponsored Links


ToolBox ShortList

Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!

Add this Page!Delete the ShortList!

Google
Web The HVAC ToolBox

Free Translation
Translate this page to Spanish French German Italian Dutch Norwegian

© The HVAC ToolBox

The content in The HVAC ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.

We appreciate any comments and tips on how to make The HVAC ToolBox a better information source. Please contact us by email if You find any faults, inaccurate, or otherwise unacceptable information.

Editor email

5 12 1